Overview
Product Specifications – EDB24045 – Square D Bolt-On Circuit Breaker
-
Part Number:
EDB24045 -
Manufacturer:
Schneider Electric / Square D -
Family:
EDB Series -
Pole:
2 -
Amp
45 -
Volt:
480 -
Phase:
1
-
Category:
Molded Case / 2-Pole -
Connection:
Bolt-On -
Type:
EDB -
Functions:
LI – Long-Time and Instantaneous -
Protection:
Thermal Magnetic -
AIC Ratings:
18kA@480V | 18kA@277V | 25kA@240V | 25kA@120V
Dimensions
-
Dimensions (HxWxD):
5.66″ x 1.96″ x 4.05″
-
Weight:
4lbs
Standards
Additional Details
-
Protection Type:
Short-Circuit / Overload -
Module Type:
E-Frame -
Trip Unit Rating:
875 Amp -
Line Rated Current:
45 Amp -
Maximum Operating Voltage:
480Y/277 V AC -
Mounting Mode:
Bolt-On
-
Product Destination:
Square D NF Panelboard -
Electrical Connection:
Aluminum Lugs -
Holding Current:
270 Amp -
Local Signaling:
Trip Indicator -
Circuit Breaker Application:
HID-Rated / HACR-Rated -
AWG Gauge:
AWG 12…AWG 6 Aluminum | AWG 14…AWG 6 Copper
Product Description – EDB24045 – Square D Bolt-On Circuit Breaker
Schneider Electric / Square D’s EDB24045 bolt-on molded case circuit breaker is a reliable and easy-to-install device designed for use in Square D NF Panelboards. This circuit breaker is CSA-rated, HID-rated and HACR-rated, and UL Listed as High-Intensity Discharge.
The EDB24045 is a 2-pole bolt-on circuit breaker, rated at 45A at a system voltage of 480Y/277V AC. The circuit breaker has a thermal-magnetic trip unit and a signal indicator to indicate when a trip occurred. The device has a hold current of 270A (the maximum current the breaker can be held at to ensure a trip will occur) and a trip current of 875A (the current value when the breaker is guaranteed to trip).
Square D’s EDB24045 circuit breaker is calibrated for 40 degrees C and has aluminum lugs with a terminal lug rating of AWG 12…AWG 6 (aluminum) and AWG 14…AWG 6 (copper).